DH Water Condensing Chillers Semi-Hermetic Compressors, R-22 Refrigerant |
| Model |
Units |
30WC |
50WC |
75WC |
100WC |
100WCD |
150WC |
150WCD |
200WC |
200WCD |
250WC |
300WC |
300WCD |
| Rated Capacity @ 50oF |
Tons |
3.8 |
6 |
8.1 |
10.5 |
11.2 |
15.2 |
16 |
18.3 |
20.4 |
22.5 |
30 |
30.2 |
| Rated Capacity @ 50oF |
BTU/Hr |
45,600 |
7,200 |
97,200 |
126,000 |
134,000 |
182,400 |
192,000 |
220,000 |
245,000 |
270,000 |
360,000 |
362,000 |
| Rated Capacity @ 50oF |
KiloWatts |
13.4 |
21.1 |
28.4 |
36.9 |
39.4 |
53.4 |
56.2 |
64.4 |
71.8 |
79.1 |
105.4 |
106.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Compressor |
HP |
3 |
5 |
7.5 |
10 |
2x5 |
15 |
2x7.5 |
20 |
2x10 |
25 |
30 |
2x15 |
| Standard Pump |
HP |
1/2 |
1 |
1 |
2 |
2 |
2 |
3 |
5 |
5 |
5 |
5 |
5 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Condenser Flow Rate |
|
|
|
|
|
|
|
|
|
|
|
|
|
| City Water |
GPM |
3 |
4.5 |
6 |
8 |
8 |
11 |
14 |
16 |
18 |
19 |
22 |
23 |
| Tower Water (85 degrees F) |
GPM |
11 |
18 |
24 |
32 |
32 |
46 |
54 |
64 |
72 |
75 |
87 |
105 |
| Condensor Connections |
Inches |
3/4" mnpt |
3/4" mnpt |
3/4" mnpt |
1" mnpt |
1" mnpt |
1 1 /4" mnpt |
1 1 /4" mnpt |
1 1/2 " mnpt |
1 1/2" mnpt |
2" mnpt |
2" mnpt |
2" mnpt |
| Process Connections |
Inches |
1" mnpt |
1" mnpt |
1" mnpt |
1 1/2 " mnpt |
1 1/2 " mnpt |
1 1/2 " mnpt |
1 1/2 " mnpt |
1 1/2 " mnpt |
1 1/2 " mnpt |
2" mnpt |
2" mnpt |
2" mnpt |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Full Load / Running Load Current |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 208/230V-3-60 |
Amps |
15.1/12.1 |
25.6/20.5 |
36.4/29.1 |
51.6/41.3 |
51.3/40.4 |
72.6/58.1 |
75.2/60.2 |
86.6/69.3 |
105/83.8 |
112/89.6 |
115/92.1 |
141/113 |
| 460-3-60 |
Amps |
7.6/6.1 |
13.9/11.1 |
17.7/14.2 |
25.5/20.4 |
27.5/21.4 |
36.3/29.0 |
39.4/31.5 |
43.3/34.6 |
51.8/41.4 |
56.1/44.9 |
60.1/48.1 |
70.6/56.5 |
|
|
|||||||||||||
| Tank Size |
Gal |
6 |
6 |
6 |
19 |
19 |
30 |
30 |
30 |
30 |
30 |
44 |
44 |
| Physical Size |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Length |
Inches |
40 |
44 |
52 |
52 |
68 |
72 |
72 |
72 |
72 |
72 |
80 |
80 |
| Width |
Inches |
18 |
20 |
28 |
28 |
36 |
32 |
36 |
32 |
36 |
32 |
32 |
40 |
| Height (bolt down / casters) |
Inches |
45/49 |
50/55 |
50/55 |
53/58 |
53/58 |
53/58 |
53/58 |
55/61 |
55/61 |
55/61 |
55/61 |
55/61 |
| Approx Shipping Wt |
Pounds |
700 |
900 |
1000 |
1050 |
1400 |
1600 |
1800 |
1800 |
2100 |
1900 |
2000 |
2400 |
| * For high ambient and low operating temperatures, configuration may change. Please consult factory. | |||||||||||||
![]() |
![]() |
![]() |