REFRIGERATION
SYSTEM:
Cooling
capacity BTU/Hr @ 50°F:
|
SU05
|
SU08
|
SU10
|
SU15
|
|
5,000
|
7,000
|
10,000
|
14,800
|
Design
temperature range:
30
to 75°F leaving coolant
Design
ambient range:
40
to 95°F
Compressor:
Copeland hermetic
|
SU05
|
SU08
|
SU10
|
SU15
|
|
1/2
Hp
|
3/4
Hp
|
1
1/4 Hp
|
1
1/2 Hp
|
Condenser
Type:
Air
cooled aluminum fin, copper tube fitted with cooling
fan
Evaporator:
Fully
insulated steel shell and copper tube in tube heat
exchanger. Coolant only in contact with copper.
Pressure
Relief:
Receiver
to be fitted with fusible plug type pressure relief
device.
Capacity
Control:
On/Off
control standard Optional Hot Gas Bypass to control
+/- 1/2°F with microprocessor digital temperature
controller with programmable limits.
Expansion
valve:
Thermal
control expansion valve.
Refrigerant
piping:
All
ACR specification copper, joined with silver bearing
brazing. Service and isolation valves (2). Full
refrigerant charge
Other
features:
Desiccant
core drier
Refrigerant sight glass
Thermostat:
Electronic
microprocessor digital controller with programmable
limits.
|

Safety
Controls:
Low
pressure cut-out
Pressure relief
Compressor motor overload
Main circuit fuse
NEMA electrical enclosure
Fused line circuit
Magnetic starter
Compressor overload protection
Main power
| |
110V/1/60
|
220/1/60<
|
220/3/60
|
|
SU05
|
12
Amps
|
N/A
|
N/A
|
|
SU08
|
20
Amps
|
10
Amps
|
N/A
|
|
SU10
|
N/A
|
12
Amps
|
N/A
|
|
SU15
|
N/A
|
18
Amps
|
12
|
COOLANT
SYSTEM
Pump: Centrifugal
|
SU05
|
SU08
|
SU10/15
|
|
1/8
hp
|
1/8
hp
|
1/2
hp
|
Pressure
and flow:
| |
SU05
|
SU08
|
SU10
|
SU15
|
|
PSI
|
11
|
11
|
30
|
25
|
|
GPM
|
3
|
3
|
4
|
8
|
Coolant
piping: All Copper
Coolant
Connections: One each, on supply, return
|
SU05
|
SU08
|
SU10/15
|
|
1/2"
FPT
|
1/2"
FPT
|
3/4"
FPT
|
|
2
gal tank
|
2
gal tank
|
4
gal tank
|
PHYSICAL
Weight:
|
SU05
|
SU08
|
SU10
|
SU15
|
|
130
lbs.
|
210
lbs.
|
280
lbs.
|
300
lbs.
|
Mounting:
Skid
mounted with bolt-down lugs or casters at customer
choice.
Frame:
Structural
steel
Covers:
Galvanized
steel, painted removable for maintenance
Paint
color:
Light
Gray
OPTIONS
Hot
gas bypass temperature control
Low tank warning light
Low flow warning light and interlock
High temperature warning light
Special colors
Stainless steel exterior
|